Type S
Features

Heavy Load Termination Flexibility - Designed for machine, switchboard and other heavy load terminations.

Tubular High Pressure Solderless Connections - Accomodates wire without lugging - tapped side-walls for greater mechanical strength - electrolytically pure copper solderless connections provide 100% conductivity.

Readily Adaptable to Special Applications - Can be used for branch circuit termination with simple modification of standard terminal plate.

Combined Style Design Capability - All types can be combined with each other as well as Types H and BT.

Ratings and Wire Sizes to Match High Current Needs - Type L is rated at 100 amps/600 volts UL recognized for wire up to No. 1AWG. Type O: 125 amps/600 volts UL recognized for wire up to No.1/0AWG. Type S: 225amps/600 volts and UL recognized for wire up to 4/0AWG (Note: UL requires the use of UL recognized lugs).

Heavy Load Ratings and Wire Sizes - Type T - rated 125 amps/600 volts - has headless slotted screw - UL recognized for No. 6AWG to No. 1/0AWG wire. Type U is rated 250 amps/600 volts and features headless socket screw UL recognized for No. 6AWG to 250MCM wire.



  Recognized under the Components Program of Underwriters Laboratories, Inc. Standard 1059, Guide No.XCFR2, File No.E62557.
Guide No.184-N-90, Report No.LR39186-1.

Variations

S
Terminal bar and 3/8" hex-head screw,
Max. lug width - 1"

Terminal Designations
S Nickel-plated brass terminal bar with 3/8" plated hex-head steel screws. Accepts wire up to No. 4/0AWG.

Engineering Specifications

Wire Range: UL Recognized -
Type S -to No.4/0AWG.
Number of Terminals: 1 thru 4
Voltage Rating: 600 volts CSA and UL.
Tightening Torque: 200in.-lb
Current Rating: 225 amps
NOTE: Specifications contained herein are subject to change without notice.
Housing:
Material Phenolic
Continuous Use Temp. (UL Index) 150°C (302°F)
Flammability Rating 94V-1
Water Absorption
(24hrs. % wt. gain)
.05%
Chemical Resistance Resistant to most organic solvents.
Breakdown Voltage
Terminal - Terminal
Terminal - Ground
10,400V Typ.
10,500V Typ.

Dimensions

NOTE: Lugs are not furnished with blocks

NOTE: mm dim. are shown in parentheses.
No. of Terminals
Mounting Dimensions
Overall Dimensions
Inches
Metric (mm)
inches
Metric (mm)
1
3.440
87.38
3.940
100.08
2
5.856
148.74
6.356
161.44
3
8.271
210.09
8.771
222.79
4
10.687
271.44
11.187
284.14
Dimensions shown are +/-.030"
NOTE: Thru-bolt construction is amply strong for normal applications, but if excessive mechanical loads are expected, strain relief should be provided. Chart lists dimensions for up to six terminals per block, but longer lengths are available. Tie-down points are recommended for blocks exceeding four terminals for type U and six terminals for Type T.

How to Order
Types L, O, S, T and U terminal blocks are ordered by listing a composite number made up of the model designation followed by the number of terminals required for the application. Example: four-pole terminal block becomes stock number L-4, O-4, S-4, T-4 or U-4.

When ordering combinations of both types, the composite number is made up of both model designations followed by total number of poles and number of each type. A composite of two T terminals followed by two U terminals thus is converted to stock number TU-4 (2T, 2U). Combining these types with Types L, O, S, H and BT would follow the same ordering format. (Note - when combined with types H or BT a special adapter is required).

Click here for accessories